  Datasheet File OCR Text:
  medical ac - dc enclosed power supply 12v 400w 3 .5 ? x5 .5 ? high density mds - 400a db12 aa 1 mds - 4 0 0 adb12 aa highlights & features C C C C cb certified for worldwide use model number: mds -4 0 0 a db12 aa unit weight : 6 05g (1.34lb) dimensions ( w x l x h ): 88.9x14 0 . 0 x4 4 . 4 mm ( 3.5x5.5x1.75 inch ) general description delta ?s mds -4 00a d b12 enclosed design offers a high energy density (1 1.9 watts/in3) 3 .5 x5 .5 x1.75 inch design for type bf patient access medical products. with operating parameters of 90 to 264 vac universal input voltage, operating temperatures of - 10 to +70 degrees centigrade, and a ltitudes of up to 5000 meters (16,40 2 feet), the design is well suited for a variety of both medical and non - medical applications. other features include input surge of 300 vac, low leakage current, no - load input power < 0.5 watt, and 5 00k hour mtbf. this product is certified for emc standards en 55011 for industrial, scientific and medical (ism) radio - frequency equipment, and en 55022 for industrial technology equipment (ite) radio - frequency equipment. in addition, only recognized japanese cap acitors are used to ensure long product life. an enhanced fe ature set, includes a 5 volt/ 2 amp standby output, 12 volt/0.6 fan output, remote on/off, remote sense, and a power good signal that are included as part of the standard product. the design, whi ch has protection against shock compliant with 2xmopp and type bf requirements, has both medical (with risk report available), and ite safety approvals, including curus(us&canada) /tuv/gb(china); plus, cb certificates with all national deviations. full co mpliance with rohs directive 2011/65/eu for environmental protection is included. model information (all with 5v/ 2 a standby available): model number input v oltage output v oltage forced air curr ent output mds - 4 00a d b 12 a a 90 - 2 64 v ac 12 vdc 0 - 33.33 a (with 20 cfm forced air) fan output v oltage fan output current 12 vdc 0.05 - 0.6a 1) 1) fan output will be present only when 12 v main output is available mds 4 00 a d b 12 a a delta medical power supply max wattage in the product series. 4 0 0 4 0 0 w family code a z product type d : enclosed input type code b: 3pin class i output voltage 12 for 12v revision code all parameters are specified at 25 c ambient unless otherwise noted. www. deltapsu .com ( november 201 6 , rev. 0 3 )
medical ac - dc enclosed power supply 12v 400w 3 .5 ? x5 .5 ? high density mds - 400a db12 aa 2 specifications input ratings / characteristics nomina l input v oltage 100-2 4 0 v ac input v oltage range 90-2 64 v ac nominal input f r equency 50- 60hz input f r equency range 47- 63hz input cur r ent (max) 5.5 a in put surge voltage (max) 300vac for 10 0 ms full load e f ficiency (typ.) 89.5 % @ 115vac /60hz 91.5 % @ 230v ac /50hz , reference fig.1 standby power (max) 0.5w (only standby working with inhibit signal high) @ 115vac/6 0hz, 230v ac /50hz inrush cur r ent ( max ) 40 a@2 3 0 v ac, cold start input - pe(protective earth) l eakage c ur r ent (max) 0.1ma @ nc , 0.3 ma @ sfc 1 ) output - pe(protective earth) leakage current for type bf application (max) 0.1ma @ nc, 0. 5 ma @ sfc 1 ) power factor (min) 0.95 @ 115v/50hz, 230v/50hz, full load 1) n c: normal condition, sfc: single fault condition leakage current input - pe leakage current 100vac/60hz (typ) 264vac/60hz (typ) delta limit iec60601 - 1 limit normal condition 17.5 ua 43.5ua 100ua max 5000ua max single fault condition 32.9ua 90.7ua 300ua max 10000ua max output - pe leakage current for type bf application normal condition 28.5ua 86.7ua 100ua max 100ua max single fault condition 42.9ua 128.6ua 500ua max 500ua max fig.1 efficiency versus output load 50.00 60.00 70.00 80.00 90.00 100.00 25% 50% 75% 100% 115vac 230vac efficiency (%) output load (400w) all parameters are specified at 25 c ambient unless otherwise noted. www. deltapsu .com ( november 201 6 , rev. 0 3 )
medical ac - dc enclosed power supply 12v 400w 3 .5 ? x5 .5 ? high density mds - 400a db12 aa 3 output ratings / characteristics nominal output v oltage (vrated ) 12v output v oltage t olerance 3 % output power 400w max with 20 cfm air cooling line regulation (max) 0.5% load regulation (max) 1 % ripple & noise (typ.) 150mv pk -pk vrated @ full load, reference fig. 2 start -up time (max) 2 0 00ms@1 15v ac hold -up time ( min ) 1 0 ms@1 15v ac , with 400w load dynamic response (overshoot & undershoot o/p v oltage) 5 % @50 - 100% load capacitive load (max) 3000uf rise time (max) 100ms remote sense compensate up to 500mv lead drop with remote sense short and reverse connection protected . psu can work normally with remote sense pins left open. (a) 115v (measured value= 97.6 mv) (b) 230v (measured value=104mv) fig. 2 ripple & noise example , 20mhz bw ripple & noise measurement circuit 0.47uf ceramic 10uf lectrolytic ps load test fixture 5cm scope all parameters are specified at 25 c ambient unless otherwise noted. www. deltapsu .com ( november 201 6 , rev. 0 3 )
medical ac - dc enclosed power supply 12v 400w 3 .5 ? x5 .5 ? high density mds - 400a db12 aa 4 mechanical case cover enclosed cover(spcc) dimensions (w x l x h typ. ) 88.9x14 0 . 0 x4 4 . 4 mm ( 3.5x5.5x1.7 5 inch ) unit weight 6 05g (1.34lb) indicator na cooling system tbd environment surrounding air temperature operating absolute maximum/minimum rating. - 10c to + 7 0c . linearly derate from 100% load at 5 0c, to 50% load at 7 0c (2.5%/ degree centigrade) for forced air . note: see power de - rating curves below storage - 40 c to + 8 5c operating humidity 5 - 9 5 % rh (non - condensing) operating altitude 5 ,000 m eters (16402 fts) shock test (non - operating) 50g, 11ms, 3 shocks for each direction vibration (operating) 5 - 500hz, 2grms, 15 minute for each three axis power de - rating curve all parameters are specified at 25 c ambient unless otherwise noted. www. deltapsu .com ( november 201 6 , rev. 0 3 )
medical ac - dc enclosed power supply 12v 400w 3 .5 ? x5 .5 ? high density mds - 400a db12 aa 5 protections overvoltage ( max ) 1 3 5 % of rated voltage , latch mode overload / overcurrent ( max ) main output 1 6 0 % of rated current standby 3 a max hiccup mode ( non - latching, auto - recovery ) over temperature latch mode short circuit hiccup mode, ( non - latching , auto - recovery) reliability mtbf(minimum) at 115v ac , 40 0w, 35 c, 20 cfm air flow 5 00 khrs based on telecordia sr -332 operating life at 115vac, 400w , ambient 25 c , 20 cfm air flow 26,280 hrs safety standards / directives medical safety iec60601 - 1 2 nd and 3 rd , and 3 rd +a1 ed ition cb report tuv en60601 - 1:2006 ul60601 - 1+can/csa 60601- 1: (ed.3.2005) ite safety iec60950 - 1 cb report tu v60950 -1 ul60950 - 1+can/csa60950- 1 gb4943.1 - 2011, gb9254 - 2008, gb17625.1 - 2003 ce mdd directive 93/42/eec environmental rohs directive 2011/65/eu compliant galvanic isolation input to/output (2xmopp) input to/ground (1xmopp) output to/ground (1xmopp) 4000 vac 1500vac 1 ) 1500vac ( type bf application rated) 1) psu can support poe applications with primary to fg 25 00 vac test. all parameters are specified at 25 c ambient unless otherwise noted. www. deltapsu .com ( november 201 6 , rev. 0 3 )
medical ac - dc enclosed power supply 12v 400w 3 .5 ? x5 .5 ? high density mds - 400a db12 aa 6 emc ( compliant with iec 60601 - 1 - 2 4th ed. requirements ) emc / emissions en550 11/ en550 22, fcc title 47 : class b harmonic current emissions iec61000 - 3 -2 meet class d limit immunity to voltage flicker iec 61000- 3 -3 electrostatic discharge iec61000 - 4 -2 level 4 criteria a 1) air discharge: 15 kv contact discharge: 8 kv radiated field iec61000 - 4 -3 criteria a 1 ) 80mhz - 2700mhz, 10v/ m am modulation 385mhz - 5785mhz, 28v/ m pulse mode and other modulation electrical fast transient / burst iec61000 - 4 - 4 level 3 criteria a 1) : 2kv surge iec61000 - 4 -5 level 3 criteria a 1) common mode 3 ) : 2kv differential mode 4 ) : 1kv conducted iec61000 - 4 -6 level 2 criteria a 1) 150khz - 80mhz, 3 vrms , 6vrms at ism bands and amateur radio bands power frequency magnetic fields iec61000 - 4 -8 criteria a 1) magnetic field strength 3 0 a/ m voltage dips iec61000 - 4 -11 criteria a 1) 0% u t , 0.5 cycle ( 10ms ) , 0 o /45 o /90 o /135 o /180 o /225 o /270 o /315 o /360 o criteria b 2 ) 0% u t , 1 cycle ( 20ms ), 0 o criteria b 2) 70% u t , 25 cycle ( 500ms ), 0 o criteria b 2) 0 % u t , 250 cycle ( 50 0 0ms ), 0 o 1 ) criteria a: normal performance within the specification limits 2) criteria b : output out of regulation, or shuts down during test. automatically restore to normal operation after test. 3) asymmetrical: common mode (line to earth) 4 ) symmetrical: differential mode (line to line) all parameters are specified at 25 c ambient unless otherwise noted. www. deltapsu .com ( november 201 6 , rev. 0 3 )
medical ac - dc enclosed power supply 12v 400w 3 .5 ? x5 .5 ? high density mds - 400a db12 aa 7 dimensions w x l x h : 88.9 x 1 40.0 x 44.4 mm mechanical drawing (3pin input type ) notes D dimensions are in mm (inches) D there are two locations where assembled power supply is connected to the customers product a. bottom mounting, use (4x) m3 screws to affix assembled power supply to product?s enclosure. extruded hole with thread must be withstand 9kgf -cm (7 . 81lb -in ) min. m aximum allowed screw penetration is 3.5mm (0.138 inch). b. side mounting, use (2x) m3 screws to affix one side of assembled power supply to the product?s enclosure. extruded hole with thread must be withstand 9kgf -cm ( 7 . 81 lb -in ) min. maximum allowed screw penetration is 3.5mm (0.138 inch). all parameters are specified at 25 c ambient unless otherwise noted. www. deltapsu .com ( november 201 6 , rev. 0 3 )
medical ac - dc enclosed power supply 12v 400w 3 .5 ? x5 .5 ? high density mds - 400a db12 aa 8 input connector cn1 control and standby connector cn101 pin 1 neutral pin 1 remote sense + pin 2 line pin 2 remote sense C cn1 mates with molex housing 26033031 and molex series 6838 crimp terminals. input line can also be connected to pin 1, and input neutral can be connected to pin 2 pin 3 power good + pin 4 power good - (dc rtn) pin 5 remote on_off/inhibit + pin 6 remote on_off/inhibit - (dc rtn) pin 8 dc rtn output connector pin 9 5v standby cn102 vo pin 10 dc rtn cn103 dc rtn cn10 1 mates with molex housing 1041421000 and molex series 104539 crimp terminals. force required to tighten the screws is 7~8kgf.cm(6.1~7.0inch - lb) fan connector cn104 p in1 12v fan p in2 dc rtn cn 104 mates with jst housing phr - 2 and jst sph - 002t - p0.5s terminals. cn2: pingoo d : jp - 13t or equivalent mate with kst :fdfnyd1 - 187 or other applicable connectors all parameters are specified at 25 c ambient unless otherwise noted. www. deltapsu .com ( november 201 6 , rev. 0 3 )
medical ac - dc enclosed power supply 12v 400w 3 .5 ? x5 .5 ? high density mds - 400a db12 aa 9 functions start - up time the time required for the output voltage to reach 90% of its set value, after the input voltage is applied. rise time the time required for the output voltage to change from 10% to 90% of its set va lue. hold - up time hold up time is the time when the ac input collapses and output voltage retains regulation for a certain period of time. the time req uired for the output to reach 9 0 % of its set value, after the input voltage is removed. graph illustrating the start - up time, rise time, and hold- up time dynamic response the power supply output voltage will remain within 5 % of its steady state value, when subjected to a dynamic load 50 to 100% of its rated current. 50 to 100% load inrush current inrush current is the peak, instantaneous, input current measured and, occurs when the input voltage is first applied. for ac input voltages, the maximum peak value of inrush current will occur during the first half cycle of the applied ac voltage. this peak value decreases exponentially during subsequent cycles of ac voltage. overvoltage protection the power supply?s overvoltage circuit will be activated when its internal feedback circuit fails. the output voltage shall not exceed its specifications defined on page 4 under ?protections?. power supply will latch off, and require removal/re - application of input ac voltage in order to restart. all parameters are specified at 25 c ambient unless otherwise noted. www. deltapsu .com ( november 201 6 , rev. 0 3 )
medical ac - dc enclosed power supply 12v 400w 3 .5 ? x5 .5 ? high density mds - 400a db12 aa 10 short circuit protection the power supply?s output olp/ocp function also provides protection against short circuits. when a short circuit is applied, the output current will operate in ?hiccup mode?, as shown in the illustration in the olp/ocp section on this page. the power supply will return to normal operation after the short circuit is removed . overload & overcurrent protections the power supply?s overload (olp) and overcurrent (ocp) protections will be activated before output current under 1 6 0 % of i o (max load). upon such occurrence, v o will start to dro p. o nce the power supply has reached its maximu m power limit, the protection will be activated and the power supply will go into ?hiccup mode? (auto - recovery). the power supply will rec over once the fault condition causing the olp and ocp is removed and i o is back within th e specified limit. additionally, if the i out is <1 6 0% but >1 0 0% for a prolong period of time (depending on the load), the over temperature protection (otp) will be activated due to high temperature on critical components. then, t he power supply will be latch ed off, and require recycling of input voltage to restart it. over temperature protection as mentioned above, the power supply also has over temperature protection (otp). this is activated when the overload condition persists for an extended duration and the output current is below the overload trigger point but >100% load. in the event of a hi gher operating temperature condition at 100% load, the power supply will run into otp when the surrounding air temperature is higher than the operating temperature. when activated, the output voltage will go into latch mode until the input voltage is remov ed; then, reapplied , and the surrounding air temperature drops to its normal operating temperature. power good power good+ pin is an open collector transistor (40v/600ma rating). a resistor (suggested value 10kohm, 1/8w) can be added between 5 v standby pin (or, other available pull - up voltage that is no greater than 30v ) and the power good+ pin (refer to figure below). value of pull - up resistor may have to be adjusted, depending on voltage used, and other end - use conditions of the power good+ pin connection to the product. when ac input is on, power good+ pin will be high. when ac input is off, power good+ pin will be l ow. there will be a minimum of 3 milliseconds between the time the power good goes to low level, and the time when the output reaches 90% of its rated value. remote on_off/inhibit remote on_off/inhibit can be used to enable or disable only the main output. when the main output is disabled, the +5v standby output will continue to operate. this signal can be pulled down to a low level of 0.3 volts, or shorted to dc - return, in order for the main output to be enabled; and, floated (no connection to the signal), or pulled up to a value greater than or equal to 3 volts, in order to disable the main output. remote sense remote sense feature can be used to compensate for the extra voltage drop on output wires that are connected from the main output terminals, to the load. with wires connected from the remote sense pins, at the same locations as the wires from the main output, the remote sense function can compensate up to 500mv voltage drop. the power supply will not be damaged if the remote sense pins are shorted, o r if a reverse/inverted polarity connection is made to the load. all parameters are specified at 25 c ambient unless otherwise noted. www. deltapsu .com ( november 201 6 , rev. 0 3 )
medical ac - dc enclosed power supply 12v 400w 3 .5 ? x5 .5 ? high density mds - 400a db12 aa 11 certificate all delta medical power products conform to the european directive 2011/65/eu. rohs is the abbreviation for ?restriction of the use of certain h azardous substances delta has been certified as meeting the requirement of iso 13485: 2003 and en iso 13485:2012 for the design and manufacture of switching power supply and adaptor for medical device. in addition to a ul total certification program (tcp) approved client laboratory for iec60950 and iec60065. delta also has participated ul client test data program (cdtp) for iec 60601 all parameters are specified at 25 c ambient unless otherwise noted. www. deltapsu .com ( november 201 6 , rev. 0 3 )


▲Up To Search▲   

 
Price & Availability of MDS-400ADB12AA

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X